| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| CWE-611 Improper Restriction of XML External Entity Reference vulnerability exists that could cause information disclosure of server-side file contents when an attacker with a Data Center Expert user account submits crafted XML payloads to SOAP service endpoints. |
| A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections. |
| An authentication bypass by capture-replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download. |
| ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets. |
| Systems with microprocessors utilizing speculative execution and speculative execution of memory reads before the addresses of all prior memory writes are known may allow unauthorized disclosure of information to an attacker with local user access via a side-channel analysis, aka Speculative Store Bypass (SSB), Variant 4. |
| A CWE-334: Small Space of Random Values vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller. |
| A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys. |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service of the controller when reading specific memory blocks using Modbus TCP. |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon Quantum, Modicon Premium (see security notification for specific versions) which could cause a Denial of Service when writing specific physical memory blocks using Modbus TCP. |
| A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus. |
| A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium. |
| A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service when an invalid private command parameter is sent to the controller over Modbus. |
| An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet interface while the Ethernet/IP adapter is activated. |
| A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller. |
| A CWE-287: Improper Authentication vulnerability exists in PowerLogic PM55xx, PowerLogic PM8ECC, PowerLogic EGX100 and PowerLogic EGX300 (see security notification for version infromation) that could cause loss of connectivity to the device via Modbus TCP protocol when an attacker sends a specially crafted HTTP request. |
| A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists in PowerLogic PM55xx, PowerLogic PM8ECC, PowerLogic EGX100 and PowerLogic EGX300 (see security notification for version infromation) that could allow an attacker administrator level access to a device. |
| A CWE-319: Cleartext transmission of sensitive information vulnerability exists in PowerLogic ION7400, ION7650, ION7700/73xx, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions), that could cause disclosure of user credentials when a malicious actor intercepts Telnet network traffic between a user and the device. |
| A CWE-326: Inadequate Encryption Strength vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller. |
| A CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists in the Web Server on Modicon M340, Modicon Quantum and Modicon Premium Legacy offers and their Communication Modules (see notification for details) which could cause write access and the execution of commands when uploading a specially crafted file on the controller over FTP. |
| A CWE-787: Out-of-bounds Write vulnerability exists in the Web Server on Modicon M340, Modicon Quantum and Modicon Premium Legacy offers and their Communication Modules (see notification for details) which could cause corruption of data, a crash, or code execution when uploading a specially crafted file on the controller over FTP. |