Filtered by vendor Socomec
Subscriptions
Filtered by product Diris A-40
Subscriptions
Total
2 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2026-2491 | 1 Socomec | 1 Diris A-40 | 2026-03-16 | N/A |
| Socomec DIRIS A-40 HTTP API Authentication Bypass Vulnerability. This vulnerability allows network-adjacent attackers to bypass authentication on affected installations of Socomec DIRIS A-40 power monitoring devices. Authentication is not required to exploit this vulnerability. The specific flaw exists within the web API implementation, which listens on TCP port 80 by default. The issue results from the lack of authentication prior to allowing access to functionality. An attacker can leverage this vulnerability to bypass authentication on the system. Was ZDI-CAN-23993. | ||||
| CVE-2019-15859 | 1 Socomec | 2 Diris A-40, Diris A-40 Firmware | 2024-11-21 | 9.8 Critical |
| Password disclosure in the web interface on socomec DIRIS A-40 devices before 48250501 allows a remote attacker to get full access to a device via the /password.jsn URI. | ||||