| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| The HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to cause a denial of service (daemon crash) via a crafted HTTP request. |
| SQL injection vulnerability in the login screen in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |
| Buffer overflow in a third-party ActiveX component in Siemens SIMATIC RF-MANAGER 2008, and RF-MANAGER Basic 3.0 and earlier, allows remote attackers to execute arbitrary code via a crafted web site. |
| Siemens RuggedCom Rugged Operating System (ROS) before 3.12, ROX I OS through 1.14.5, ROX II OS through 2.3.0, and RuggedMax OS through 4.2.1.4621.22 use hardcoded private keys for SSL and SSH communication, which makes it easier for man-in-the-middle attackers to spoof servers and decrypt network traffic by leveraging the availability of these keys within ROS files at all customer installations. |
| Invensys Wonderware InTouch 2012 R2 and earlier and Siemens ProcessSuite use a weak encryption algorithm for data in Ps_security.ini, which makes it easier for local users to discover passwords by reading this file. |
| Siemens Simatic WinCC and PCS 7 SCADA system uses a hard-coded password, which allows local users to access a back-end database and gain privileges, as demonstrated in the wild in July 2010 by the Stuxnet worm, a different vulnerability than CVE-2010-2568. |
| Multiple cross-site scripting (XSS) vulnerabilities in unspecified web applications in Siemens WinCC 7.0 SP3 before Update 2 allow remote attackers to inject arbitrary web script or HTML via vectors involving special characters in parameters. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account. |
| Siemens COMOS before 9.1 Patch 413, 9.2 before Update 03 Patch 023, and 10.0 before Patch 005 allows remote authenticated users to obtain database administrative access via unspecified method calls. |
| Multiple directory traversal vulnerabilities in Siemens WinCC 7.0 SP3 before Update 2 allow remote authenticated users to read arbitrary files via a crafted parameter in a URL. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials. |
| RuggedCom Rugged Operating System (ROS) 3.10.x and earlier has a factory account with a password derived from the MAC Address field in the banner, which makes it easier for remote attackers to obtain access by performing a calculation on this address value, and then establishing a (1) TELNET, (2) remote shell (aka rsh), or (3) serial-console session. |
| Multiple cross-site scripting (XSS) vulnerabilities in the HMI web application in Siemens WinCC (TIA Portal) 11 allow remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. |
| Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. |
| The XPath functionality in unspecified web applications in Siemens WinCC 7.0 SP3 before Update 2 does not properly handle special characters in parameters, which allows remote authenticated users to read or modify settings via a crafted URL, related to an "XML injection" attack. |
| Buffer overflow in the DiagAgent web server in Siemens WinCC 7.0 SP3 through Update 2 allows remote attackers to cause a denial of service (agent outage) via crafted input. |
| Buffer overflow in the WebClient ActiveX control in Siemens Tecnomatix FactoryLink 6.6.1 (aka 6.6 SP1), 7.5.217 (aka 7.5 SP2), and 8.0.2.54 allows remote attackers to execute arbitrary code via a long string in a parameter associated with the location URL. |
| AscoServer.exe in the server in Siemens SiPass integrated MP2.6 and earlier does not properly handle IOCP RPC messages received over an Ethernet network, which allows remote attackers to write data to any memory location and consequently execute arbitrary code via crafted messages, as demonstrated by an arbitrary pointer dereference attack or a buffer overflow attack. |