| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability was discovered in Siemens SiPass integrated (All versions before V2.70) that could allow an attacker with local access to the SiPass integrated server or SiPass integrated client to potentially obtain credentials from the systems. |
| An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow unauthenticated remote attackers to obtain sensitive device information over the network. |
| Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually. |
| An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability. |
| Multiple buffer overflows in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allow attacker with local access to the system to execute arbitrary code with AMT execution privilege. |
| An Improper Authentication issue was discovered in Siemens SIMATIC CP 44x-1 RNA, all versions prior to 1.4.1. An unauthenticated remote attacker may be able to perform administrative actions on the Communication Process (CP) of the RNA series module, if network access to Port 102/TCP is available and the configuration file for the CP is stored on the RNA's CPU. |
| A vulnerability was discovered in Siemens SIMATIC WinCC (V7.3 before Upd 11 and V7.4 before SP1), SIMATIC WinCC Runtime Professional (V13 before SP2 and V14 before SP1), SIMATIC WinCC (TIA Portal) Professional (V13 before SP2 and V14 before SP1) that could allow an authenticated, remote attacker who is member of the "administrators" group to crash services by sending specially crafted messages to the DCOM interface. |
| A vulnerability was discovered in Siemens XHQ server 4 and 5 (4 before V4.7.1.3 and 5 before V5.0.0.2) that could allow an authenticated low-privileged remote user to gain read access to data in the XHQ solution exceeding his configured permission level. |
| Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. |
| A non-privileged user of the Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could perform a persistent Cross-Site Scripting (XSS) attack, potentially resulting in obtaining administrative permissions. |
| A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. A directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices. |
| The rate limiting feature in NTP 4.x before 4.2.8p4 and 4.3.x before 4.3.77 allows remote attackers to have unspecified impact via a large number of crafted requests. |
| The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow remote attackers to perform actions with the privileges of an authenticated user, provided the targeted user has an active session and is induced into clicking on a malicious link or into visiting a malicious website, aka CSRF. |
| The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow an authenticated user to perform stored Cross-Site Scripting attacks. |
| A vulnerability was discovered in Siemens ViewPort for Web Office Portal before revision number 1453 that could allow an unauthenticated remote user to upload arbitrary code and execute it with the permissions of the operating-system user running the web server by sending specially crafted network packets to port 443/TCP or port 80/TCP. |
| A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2). The existing TLS protocol implementation could allow an attacker to read and modify data within a TLS session while performing a Man-in-the-Middle (MitM) attack. |
| An Improper Input Validation issue was discovered in Siemens SIMATIC PCS 7 V8.1 prior to V8.1 SP1 with WinCC V7.3 Upd 13, and V8.2 all versions. The improper input validation vulnerability has been identified, which may allow an authenticated remote attacker who is a member of the administrators group to crash services by sending specially crafted messages to the DCOM interface. |
| An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow unauthenticated remote attackers to execute arbitrary code on the affected device. |
| A vulnerability was discovered in Siemens SiPass integrated (All versions before V2.70) that could allow an attacker with network access to the SiPass integrated server to bypass the authentication mechanism and perform administrative operations. |
| Siemens SINUMERIK Integrate Operate Clients between 2.0.3.00.016 (including) and 2.0.6 (excluding) and between 3.0.4.00.032 (including) and 3.0.6 (excluding) contain a vulnerability that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack. |